Hello, welcome to the official website of Rijian Firefighting

产品中心 产品中心
/
/
/
Pressure proportional mixing device\foam tank

CLASSIFICATION

All categories
Number of views:
1000

Pressure proportional mixing device\foam tank

PHYM series pressure proportional mixing device (hereinafter referred to as mixing device) has the characteristics of stable performance, wide range of applicable flow pressure and low pressure loss. Type low-expansion foam generator, PQ-type air foam gun or PP-type foam gun form various high, medium and low expansion foam fire extinguishing systems. The mixing device can be divided into horizontal type and vertical type according to the installation form, and can be divided into three types according to the internal structure: integral type, partition type and diaphragm type. According to the operation form, it can be divided into manual operation and automatic operation (electric or pneumatic). ), the company's factory standard configuration is AC220V electric ball valve. The storage tank volume varies from 1m3 to 10m3.
Retail price
0.0
Market price
0.0
Number of views:
1000
Product serial number
Quantity
-
+
Stock:
0
Services line: 400-6148-119
WeChat official account
1
Detailed
Parameters

1. Product overview

The pressure proportional mixing device is used to store the foam liquid and replace the foam liquid with the water supply of the fire pump group through the pressure proportional mixer, and mix it with the water supply in a certain proportion to form a foam mixture. It can be combined with foam generator, foam generator, air foam gun or foam gun to form various high, medium and low multiple foam fire extinguishing systems. The system has been used in petrochemical enterprises, ports, terminals, oil depots, airports and other places. are widely used.

The pressure type proportional mixing device is easy to install, use and maintain, the built-in capsule has excellent corrosion resistance, economical cost and stable and reliable performance.

The pressure proportional mixing device can be divided into horizontal type and vertical type according to the structural form. Users can choose according to the actual configuration needs and the location of the installation space.

 

The meaning of the pressure type proportional mixing device model:

PHYM - (L) - □□ / □□

Pressure Proportional Mixing Device - Vertical - Mixed Liquid Flow (L/s) / Foam Tank Volume (m3)

 

2. Working principle of pressure proportional mixing device

When the fire-fighting pressure water passes through the equipment, a part of it enters the tank through the water inlet valve, and the foam liquid is pressed out of the capsule through the liquid outlet pipeline into the proportional mixer and mixed with the pressure water flowing through the proportional mixer to form a foam mixture, which is transported. Give foam generating equipment.

 

Working principle diagram of pressure water proportional mixing device

 

1

 

3. Performance parameter table of pressure proportional mixing device

Model

Mixed liquid flow range (L/s)

Working pressure range

Mix ratio (%)

Pressure drop (MPa)

Tank volume (L)

Proportional mixer diameter (mm)

Style

PHYM-32/10

10~32

0.6~1.2

6

≤0.15

1000

100

horizontal

PHYM-32/20

10~32

0.6~1.2

6

≤0.15

2000

100

PHYM-32/30

10~32

0.6~1.2

6

≤0.15

3000

100

PHYM-48/30

12~48

0.6~1.2

3

≤0.15

3000

150

PHYM-48/50

12~48

0.6~1.2

6

≤0.15

5000

150

PHYM-64/40

16~64

0.6~1.2

6

≤0.15

4000

150

PHYM-64/60

16~64

0.6~1.2

6

≤0.15

6000

150

PHYM-64/76

16~64

0.6~1.2

6

≤0.15

7600

150

PHYM-80/80

24~80

0.6~1.2

6

≤0.15

8000

200

PHYM-100/100

32~100

0.6~1.2

3

≤0.15

10000

200

PHYM-100/100

48~100

0.6~1.2

6

≤0.15

10000

200

PHYML32/10

10~32

0.6~1.2

3

≤0.15

1000

100

vertical

PHYML32/20

10~32

0.6~1.2

3

≤0.15

2000

100

Note: The above are the performance parameters of common models. For other specific models, please contact our company.

Keyword:
foam tank
Scan the QR code to read on your phone
We could not find any corresponding parameters, please add them to the properties table

Related Products

 Anti foaming foam extinguishing agent 6% SAR -8 C
Anti foaming foam extinguishing agent 6% SAR -8 C
First, basic functions: Brief description: 6% S/AR type foam extinguishing agent is a kind of fire extinguishing agent with high solubility and high quality. It can mix 6 volumes with 94 volumes of fresh water to extinguish the fire of polar or solvent soluble fuels such as alcohols, ketones, esters, ethers and other flammable liquids. It can also be used to extinguish non-polar hydrocarbon and oil fire. It is a general foam extinguishing agent. 6% S/AR foam extinguishing agent is a kind of fire extinguishing agent containing special biopolymers. The foam quality produced by this polymer has better stability and heat resistance, fire resistance and sealing performance than ordinary foam. Second, characteristics 1。 The low power liquid-resistant foam has the smallest stirring energy. 2。 It can quickly overwhelm the flame quenching oil fire in a short time. 3。 Suitable for mixing with clean water. 3。 Standard foam proportioning mixer and other foaming devices are compatible. 4。 The 6% S/AR type anti foam foam extinguishing agent is versatile foam extinguishing agent, which can simplify the B fuel fires that are not known or mixed with oil and polar solvents in the fire field. 5。 The storage time is 2-3 years. Third, the physical and chemical properties of fire extinguishing agent Appearance - light yellow paste Specific gravity (20 ℃), g / cm 3-1.01-1.10 PH value (20 ℃) ---- 6-9.5 Anti freezing and melting performance -- no visible stratification and heterogeneous Fluidity ---- the flow is greater than the standard reference solution Foaming multiple ------- the deviation from the characteristic value shall not be greater than 1.0 , or not greater than the characteristic value 20% 25% liquid separation time, min -- the deviation from the characteristic value shall not be greater than 20% Fire extinguishing time (acetone), min -----------≤ 3 Anti burning time (acetone), min -----------≥ 10 Fire extinguishing time (120# solvent oil), min -- strong application ≤ 3, slow application ≤ 5 Anti burning time (120# solvent oil), min -- slow release ≥ 10 Freezing point, ℃------------------------------------------------------------------ Service temperature, ℃---------- freezing point + 5 ~ 40 Fourth, product application scope: The S/AR6% type anti foam foam extinguishing agent is mainly used to extinguish fire such as alcohols, esters, aldehydes, ethers, amines, organic acids, heterocyclic and other polar (or water-soluble) solvents. It can also fight non-polar hydrocarbon and oil fires. It is a general type foam extinguishing agent. It can be applied to large scale chemical industry, petrochemical industry, chemical fiber enterprise, and numerous small and medium-sized chemical plants, paint factories, alcohol factories, etc. Chemical products warehouse and other places. Its general performance can simplify the remediation of class B fuel fires that are unknown or mixed with oils and polar solvents.
 Cabinet heptafluoropropane gas fire extinguishing system
Cabinet heptafluoropropane gas fire extinguishing system
Product Name: cabinet heptafluoropropane gas fire extinguishing system Specification and model: GQQ40 / 70 / 90 / 100 / 120 / 150 / 180; Basic functions: First, brief description: It is suitable for the installation of high-efficiency propane fire-extinguishing devices in the places where there is no need of fluorine gas tank and stain, and it is not suitable for the installation of high-efficiency propane fire-extinguishing devices, and there is no need for installation and maintenance. It is suitable for the places where there is no need for fluorine gas tank and stain. It is a cabinet type fire extinguishing device that integrates the components of fire extinguishing agent storage container, spraying pipeline, nozzle and valve driving device and is connected with the automatic fire alarm controller to realize automatic control, measurement and fire extinguishing. Since the fire extinguishing agent storage bottle is placed in the cabinet, for small protection areas of different sizes, select single bottle groups with different volumes for protection, which can reduce the floor area; The nozzle adopts multi hole type, which can make the fire extinguishing agent fill the whole protection area quickly and evenly; Like the hanging fire extinguishing device, it has the characteristics of simple construction and installation and small project investment. Second, product application It is widely used in electronic computer room, communication room, data warehouse, power distribution room, generator room, library and archives and other valuable equipment rooms. Third, product maintenance 1. Inspection (1) Daily appearance and pressure indication of the device shall be checked by trained personnel every day. (2) Check the pressure gauge at least once a quarter. If the pointer exceeds the green area or is used, entrust the manufacturer or a fire engineering unit trained and qualified for professional installation to repair it. (3) Weigh and check the fire extinguishing agent storage bottle once a year. If the weight of the storage bottle decreases by more than 5% of the total weight, the storage bottle must be refilled or replaced; Conduct an action test on the solenoid valve of the electromagnetic fire extinguishing device every year, and continue to use it after passing the test. (4) The storage bottle shall be inspected regularly according to the regulations on safety supervision of gas cylinders and other relevant national standards. It can be used only after it is qualified. If there is rust, the storage bottle shall be treated with rust prevention. While checking the storage bottle, conduct hydraulic strength test on all valves as required. 2. Maintenance (1) Fire extinguishing devices must always be in good working condition, and maintenance personnel must be specially trained. Any failure or damage to the fire extinguishing device must be repaired in time and recorded in detail. (2) After the fire-fighting equipment is trained or installed by the entrusted fire-fighting plant, it shall obtain the professional qualification of fire-fighting equipment.

留言反馈

Username used for comment:
客户留言
Description:
验证码
返回顶部
Copyright @2022 Guangzhou Rijian Firefighting Equipment Co.,Ltd. All Rights Reserved 粤ICP备2022033660号-1 Powered by 300.cn SEO